PVS Series Rack

Air Conditioner

Provides stable and reliable temperature and humidity regulation services for micro-data centers
Features
Specifications
Download

The PVS series rack air conditioner is a special air conditioner for circulating cooling the internal air flow of the cabinet, it provides stable and reliable temperature and humidity regulation services for micro-data centers, and improves the stability and reliability of all kinds of equipment in micro-data.

Safe and reliability
  • Mainstream brands are used for key components, making operation more stable and reliable
  • Using R410A green refrigerant, in line with international green refrigerant requirements
  • Standard with RS485 interface, support remote centralized control, call self-starting, timed power on and off
  • Advanced microprocessor controller with multi-level password protection to prevent misuse
Diversified configuration
  • Covering multiple cooling range segments, suitable for different power cabinet applications
  • Standard configuration of the upflow supply and horizontal airflow supply, optional front air supply form
  • A wide variety of options
High efficiency and energy saving
  • Standard EC fan, lower noise, better airflow organization, accurate automatic control of airflow output
  • High-efficiency DC inverter compressor, real-time adaptation to changes in heat load in the cabinet, infinitely adjustable refrigeration capacity
  • Equipped with electronic expansion valve to quickly and precisely adjust the system refrigerant flow, saving 30% energy compared with traditional expansion valve
  • Adopt large area "V" shape evaporator design, make heat exchange faster and more efficient
High adaptability
  • Rack-mounted pull-out design for easy handling and maintenance
  • Support single cabinet and multi-cabinet cooling applications, support cabinet online expansion, business without interruption
  • Compact structure, effectively reducing the occupation of valuable U space in the cabinet
  • Working power supply supports 50/60Hz voltage frequency, more flexible configuration
  • Standard models are suitable for outdoor ambient temperature -20~45℃, and optional low temperature components are available to meet outdoor temperature as low as -40℃.

Operation Principle 

 

Applicable  

 

Application Scenario  

Model Unit PVS-03/PVP-05 PVS-07/PVP-10 PVS-12/PVS-018 PVS-03UH
Unit configuration Constant
Temp
Constant
Temp&Hum
Constant
Temp
Constant
Temp&Hum
Constant
Temp
Constant
Temp&Hum
Constant
Temp
Total cooling capacity kW 3,7 3,7 7,5 7,5 12,5 12,5 3,7
Sensible cooling
capacity
kW 3,7 3,7 7,5 7,5 12,5 12,5 3,7
Ton(USA) 1,05 2,13 3,55 3,55
Air volume m3/h 700 700 1350 1350 2300 2300 700
Sensible heat ratio % 100 100 100 100 100 100 100
Heating capacity kW 1 1 2 2 3 3 1
Humidification
capacity
kg/h 0,5 0,5 0,5
Compressor type / DC frequency conversion
Voltage V 220 220 220 220 220 220 220
Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Phase P 1 1 1 1 1 1 1
Full load current A 13,5 13,6 28,6 28,8 29 29 13
Unit weight kg 26 27 35 36 47 49 58
Unit width mm 440 440 440 440 440 440 440
Unit depth mm 800 800 800 800 800 800 970
Unit height mm 219(5U) 219(5U) 310(7U) 310(7U) 440(10U) 440(10U) 350(8U)

 

Outdoor unit

VCP*** Unit 5 10 18
Air volume m3/h 2800 3500 5000
Voltage V 220 220 220
frequency Hz 50/60 50/60 50/60
Phase P 1 1 1
Unit width mm 886 882 995
Unit depth mm 340 380 440
Unit height mm 605 720 1256

Test condition: The indoor dry-bulb temperature is 37°, and the relative humidity is 24%.

Working temperature: -20~45℃, less than -20℃ need to add low temperature components