PDL

Diesel Generators 22 - 500 kVA

Industrial range Powered by DEUTZ three-phase engine, soundproof, operating in automatic, manual, signal or test mode
Features
Specifications
Download

PDL Diesel Generators with Standby Power 22 — 500 kVA, engineered to provide reliable and efficient power for various industrial and commercial applications. Featuring advanced Deutz engine technology, superior fuel efficiency, and durable construction, this generator ensures a continuous and dependable power supply. Ideal for medium-scale applications requiring consistent performance and durability.

Dimensions , weights & Fuel Tank

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Model Constructure Dim“A”mm Dim“B”mm Dim“C”mm Dry Weight kg Fuel Tank
Capacity L
PDL22-5 Open set 1804 650 1306 550 135
PDL22-5 Silent set 2280 955 1250 850 90
PDL33-5 Open set 1804 650 1306 600 135
PDL33-5 Silent set 2280 955 1250 880 90
PDL44-5 Open set 1980 855 1290 700 150
PDL44-5 Silent set 2320 1050 1250 900 95
PDL55-5 Open set 1980 855 1290 750 150
PDL55-5 Silent set 2320 1050 1250 950 95
PDL66-5 Open set 1800 900 1465 1000 150
PDL66-5 Silent set 2550 1050 1250 1600 95
PDL88-5 Open set 1900 1035 1485 1120 170
PDL88-5 Silent set 2750 1100 1735 1700 170
PDL100-5 Open set 1900 1035 1485 1180 170
PDL100-5 Silent set 2750 1100 1735 1800 170
PDL110-5 Open set 2100 1045 1670 1200 200
PDL110-5 Silent set 2850 1100 1650 1800 190
PDL125-5 Open set 2220 1045 1670 1250 210
PDL125-5 Silent set 2850 1100 1650 1825 190
PDL150-5 Open set 2220 1045 1670 1350 210
PDL150-5 Silent set 3050 1100 1832 1825 190
PDL200-5 Open set 2560 1100 1750 1750 330
PDL200-5 Silent set 3320 1100 1650 2400 240
PDL220-5 Open set 2560 1100 1750 1800 330
PDL220-5 Silent set 3890 1200 2100 2650 460
PDL275-5 Open set 2710 1100 1785 1650 380
PDL275-5 Silent set 4100 1430 2080 3600 450
PDL330-5 Open set 2700 1375 2265 2450 720
PDL330-5 Silent set 4150 1550 1800 4000 650
PDL360-5 Open set 2700 1375 2265 1650 720
PDL360-5 Silent set 4250 1650 2515 3600 650
PDL400-5 Open set 2700 1375 2265 720
PDL400-5 Silent set 4250 1650 2515 650
PDL500-5 Open set 3100 1460 2140 3500 850
PDL500-5 Silent set 4362 1750 2515 4500 700

Control Module

Digital Instrumentation

  • Generating set voltage
  • Mains voltage
  • Generating set frequency
  • Generating set current
  • Battery voltage
  • Power (kVA-kW-kVAr)
  • Power factor Cos φ
  • Hours-counter
  • Engine speed r.p.m
  • Fuel level (%)

General Characteristics

Item Data
Standby Power (kVA) 22 — 500
Standby Power (kW) 18 — 400
Prime Power (kVA) 20 — 450
Prime Power (kW) 16 -360
Power Factor (Cos Phi) 0.8
Diesel Engine BFM, TCD
Frequency (Hz) 50
Rated Speed (rpm) 1500
Phase 3
Standard Voltage (V) 400/230
Available Voltages (V) 380/220 · 415/240

Power Definition

Standby Power(ESP): The standby power rating is applicable for supply emergency power in variable load applications in accordance with ISO8528-1, overload is not allowed.

Prime Power(PRP): The prime power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO8528-1.

General Engine Data
Engine brand DEUTZ
Engine model BFM, TCD
Engine type 4-stroke diesel
Governor type Electronic
Injection type Direct
Aspiration type Naturally Aspirated, Turbocharged,
Turbocharged and Air to Air charge cooling
Number of cylinders and arrangement 4-L — 8-V
Bore and stroke (mm*mm) 98 x 105 — 132 x 145
Displacement (L) 3.168 — 132X145
Cooling system Water-cooled
Lube oil consumption with full load
0.3%-1% of fuel consumption
Compression Ratio 16-18.5:1
Air Filter Dry
Fuel Consumption
Fuel Consumption @ 100% load ESP (L/H) 5.9 — 96.93
Fuel Consumption @ 100% load PRP (L/H) 5.4 — 85
Fuel Consumption @ 75% load PRP (L/H) 4 — 66.56
Fuel Consumption @ 50% load PRP (L/H) 2.8 — 43.6
Air System
Intake air flow (L/s) documentation
Cooling air flow (L/s) 1100 — 10690
Exhaust System
Maximum exhaust temperature (°C) 530 — 540
Exhaust gas flow (L/s) 69.4 — 2320
Maximum allowed back pressure (kPa) 5 — 10
Starting System
Starting power(kW) 3 — 9
Recommended battery (Ah) 60 — 120
Number of Batteries 1 — 2
Auxiliary voltage (Vdc) 12 — 24
Oil System
Engine oil capacity (L) 7.5 — 48
Cooling System
Total coolant capacity (L) 4.8(engine) — 109

Terms of use

According to the standard, the nominal power assigned by the genset is given for 25 ℃ air inlet temperature, of a barometric pressure of 100 kPA (100m A.S.L) and 30%.

Alternator Data
Number of phase 3
Power factor (Cos Phi) 0.8
Poles 4
Winding Connections (standard) Star-serie
Insulation H class
Enclosure(according IEC-34-5) IP23
Excitation system Self-excited, brushless
Voltage regulator AVR (Electronic)
No. of bearings Single bearing
Coupling system Flexible disc
Coating type
Standard (Vacuum impregnation)
Datasheet
File Name Language File Download
Union datasheets PDL generators 22 - 500 kVA ENG Download
pdl22-datasheet.pdf ENG Download
pdl33-datasheet.pdf ENG Download
pdl44-datasheet.pdf ENG Download
pdl55-datasheet.pd ENG Download
pdl66-datasheet.pdf ENG Download
pdl88-datasheet.pdf ENG Download
pdl100-datasheet.pdf ENG Download
pdl110-datasheet.pdf ENG Download
pdl150-datasheet.pdf ENG Download
pdl200-datasheet.pdf ENG Download
pdl220-datasheet.pdf ENG Download
pdl275-datasheet.pdf ENG Download
pdl330-datasheet.pdf ENG Download
pdl360-datasheet.pdf ENG Download
pdl400-datasheet.pdf ENG Download
pdl500-datasheet.pdf ENG Download